tyca /cecrones Instruction Sheet 408-8452 (was TA02078} ANP 7000 Series 4Pole Timing Relay 14FEBO1 RevO 1. INTRODUCTION Model 7024 This instruction sheet covers the installation and L1 CISBVIIIO L2 operation of the AGASTAT* 7000 Series 4Pole Timing Relays (Models 7014 and 7024). Read these instructions thoroughly before installing the relay. NOTE Dimensions in this instruction sheet are in millimeters [with inches in brackets}. Figures are V/ Drop \/ \/ not drawn to scale. Cut 2. DESCRIPTION (Figure 1) Each relay is a precise timing instrument which ii 12 balances pneumatic, electrical, and mechanical forces V VY VW W using a minimum of moving parts. When satisfactory Delay Setting performance cannot be restored, the unit should be | ; returned to Tyco Electronics for repair. ne Energized Cal 5 De-Enercized Contacts ---- Open N.C. (1-5)(2-6} Closed I i N.O. (3-5) (4-6) 1 [7 Open LL Poo Closed 4-Pole Timing Relay ret (Typ) Contacts ro Open N.C. (7-11)(8-12) K Closed N.O. (9-11)(10-12} - Open Model 701d 0 Closed Li OVVIVsTO 2 TD LINEAR TIMING RANGES W/ : on WY W Pick TIME RANGE | MODEL 70140 MODEL 7024 Up CODE WV W A 0.2 to 2 Seconds 0.1 to 1 Second B 0.7 to 7 Seconds 0.5 to 5 Seconds 11 2 Y YW W W CG 2 to 20 Seconds 1.5 to 15 Seconds Delay Setting D 10 to 100 Seconds 5 to 50 Seconds ; -- Energized | I | E 30 to 300 Seconds 20 to 200 Seconds De-Energized F 1.5 to 15 Minutes 1 to 10 Minutes N.C. (3-5)(4-6) - T Closed Contacts -- Open H 3 to 30 Minutes 3 to 30 Minutes i To ose | Not Available 6 to 60 Minutes N.O. (1-5)(2-6) 14 Open J Not Available 3 to 120 Cycles N.C. (9-11)(10-12) [- Closed K Not Available 1 to 300 Cycles Open Contacts Closed ose @ Model 7014 is available with letter calibrated dials only. The upper . (7-11 yer IT Open end of the time ranges in this model may be twice the values shown. Figure 1 (cont'd) 2001 Tyco Electronics Corporation, Harrisburg, PA. All Intemational Rights Reserved. AMP and Tyco are trademarks. *Trademark This controlled document is subject to change. For latest revision call the AMP FAX* number. TOOLING ASSISTANCE CENTER 1-800-722-1111 1of2 AMP FAX/PRODUCT INFO 1-800-622-6752 For Regional Gustomer Service, visit our website at Loc B www.tycoelectronics.comtyco / Electronics 7000 Series 4Pole Timing Rela 408-8452 AMP gneey AC COIL UNITS DC COIL UNITS 3. MOUNTING INSTRUCTIONS (Figure 2) RATED RATED Normal mounting of the relay is in a vertical position, CODE | vottace | votTage | .CO2E RATED from the back of the panel. Four No. 8-32 tapped LETTER AT60Hz | AT50 Hz LETTER | VOLTAGE holes are provided in the back plate. A 120 110 M 28 feainneie Mounting screws should not project more than 3.63 mm [5/82 in} into the back of the unit, to B 240 220 N 48 prevent internal damage. 480 - 0 24 A bracket and required screws are supplied with each D 550 - P 120 unit for mounting the unit from the front. The bracket E 94 Q 19 exlends approximately 9.52 mm [3/8 in-] from each - side of the unit. F - 17 R 60 NOTE Horizontal operation is not recommended. G - 240 8 250 H te | 550 Models 7014 and 7024 (Mounting Dimensions) | 8 - U 16 < 995 [3.25] > Ww 96 9.6 [.38] 44 4 K Dual Voltage Coil Y 6 [1.75] (Cambines A and B) 5.1 [.199] Dia l Z 220 Mig Holes 427 AC Specials L1, L2, etc. BC Specials X1, X2, etc. a LC [.50] Operational voltage range 90% to 120% for AC units: 85% to 120% cr al for DG units. o; at All units draw approximately 8 watts power at rated voltage. TsO TE alec Minimum operating voltages are based on vertically mounted Model | ~ = 147.8 7014 (ondelay) units. ~ 2-32 Mig cl (5 82] AC units drop out at approximately 50% of rated voltage. DC units 19.0 7 Holes (4) y Max drop out at approximately 40% of rated voltage. 73 76.2 , All units may be operated on intermittent duty cycle at voltages 10% 63.5 [7 [3 00] above the listed maximums. (Internittent duty maximum 50% duty [2.50] cycle and 30 minutes on time.) Colls are rated 6 Vac through 550 Vac. 1 ll fl CONTACT RATINGS ee (Contact Capacity in Amperes Resistive Loads) a CONTACT MINIMUM 100,000 | MINIMUM 1,000,000 VOLTAGE OPERATIONS OPERATIONS 84.3 30 Ve 15.0 70 [3.82] Max. 110 Vde 1.0 05 120 Vac 60 Hz 20.0 15.0 240 Vac 60 Hz 20.0 15.0 480 Vac 60 Hz 12.0 10.0 Figure 2 Inductive and capacitive loads should not have inrush currents that exceed five times nemmal operating load. Contact ratings are listed under the Underwriters Laboratories Inc. Camponent Recognition Pragram for 100,000 operations: 10 A Resistive, 240 Vac (per pole) 1/4 Horsepower, 120 Vac/240Vac (per pole) 15 A, 30 Vde (per pole) 5 A, General Pumose, 600 Vac Total load must not exceed twice the above listings per pole rating. Continuous duty rating is 25 amperes any voltage, any load. Figure 7 (end) 4, QUALIFICATIONS The 7000 Series Timing Relays are listed by Underwriters Laboratories Inc. (UL) under File No. E15631. and certified jo the Canadian Standards Association (CSA) under File No. LR29186. 5. REVISION SUMMARY Per EC 0990-1603-00: * \nitial release of instruction sheet 20f2 Rev O